The Eaton 102256 FAZ-C40/3-NA circuit breaker handles up to 40 A at 415 V AC. It is designed to provide protective circuit breaking in electrical systems. Typically used in industrial and commercial applications, it ensures safety and operational reliability.
Type |
Circuit breaker |
Additional equipment possible |
TRUE |
Ambient temperature during operating |
-25-75°C |
Built-in depth |
70.5mm |
Concurrently switching neutral conductor |
FALSE |
Connectable conductor cross section multi-wired |
1-25mm² |
Connectable conductor cross section solid-core |
1-25mm² |
Current limiting class |
3 |
Degree of protection (IP) |
IP20 |
Explosion-proof |
FALSE |
Flush-mounted installation |
FALSE |
Frequency |
50-60Hz |
Nominal current |
40A |
Nominal current - rounded value |
40A |
Nominal voltage |
415V AC |
Number of pins |
3 |
Number of poles (total) |
3 |
Number of protected poles |
3 |
Overvoltage category |
3 |
Pollution degree |
2 |
Power loss |
10.2W |
Rated Current |
40A |
Rated impulse withstand voltage Uimp |
4kV |
Rated insulation voltage Ui |
440V |
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V |
0kA |
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V |
0kA |
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V |
15kA |
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V |
15kA |
Rated voltage |
415V |
Release characteristic |
C |
Release characteristics |
C |
RoHS-compliant |
Yes |
Switch-off capacity |
15kA |
Voltage type |
AC |
Width in number of modular spacings |
3 |